If you can't view the Datasheet, Please click here to try to view without PDF Reader . |
|
Datasheet File OCR Text: |
product data sheet part number: E3602S date: 1/21/2009 revision level: 10 2c 18 solid bc flex oas flex fire alarm/life safety cable a. construction diameters b. industry approvals c. electrical properties conductor: insulation: jacket: print legend: cable: #18 awg solid bare copper 0.008 wall flexguard* 0.015 wall flexguard* 0.040 nom. carol a (r) 18 awg - - E3602S - - 75c type fplp e66 267-8 (ul) - - made in usa (date code & reverse sequential footage) 2c @ 2.25 lhl with al / pe & # 22 7/30 tc dw 0.117 nom. 0.056 nom. 0.147" +/- 0.008" temperature: suggested working voltage (vrms): conductor d.c. resistance: mutual capacitance: characteristic impedance: shield resistance: ground capacitance: 75c 300v 6.4 ohms/1000 ft nom 65.7 pf/ft @ 1khz nom 31 ohms @ 1mhz nom 6.2 ohms/1000 ft nom 118.2 pf/ft @ 1khz nom national electrical code article 760 ul standard 1424 type fplp 1 2 black red d. color code (listed as individual conductors or pairs of conduc tors) note: data are subject to change without notice. contact your customer service representative for la test information. *flexguard is a trademark of general cable corporat ion for polymer alloy insulation and jackets.
|
Price & Availability of E3602S |
|
|